A481 [Process Disp Lo]

Related Parameter(s):

b010

,

P043

Sets the value displayed in

b010

[Process Display] when the drive is running at

P043

[Minimum Freq].

Values

Default:

0.00

Min/Max:

0.00/99.99

Display:

0.01

A482 [Process Disp Hi]

Related Parameter(s):

b010

,

P044

Sets the value displayed in

b010

[Process Display] when the drive is running at

P044

[Maximum Freq].

Values

Default:

0.00

Min/Max:

0.00/99.99

Display:

0.01

A483 [Testpoint Sel]

Used by Rockwell Automation field service personnel.

Values

Default:

400

Min/Max:

0/FFFF

Display:

1

A484 [Current Limit 1]

Related Parameter(s):

P033

Maximum output current allowed before current limiting occurs.

Values

Default:

Drive Rated Amps x 1.1 (Normal Duty); Drive Rated Amps x 1.5 (Heavy Duty)

Min/Max:

0.0/Drive Rated Amps x 1.5 (Normal Duty); Drive Rated Amps x 1.8 (Heavy Duty)

Display:

0.1 A

A485 [Current Limit 2]

Related Parameter(s):

P033

PowerFlex 525 only.

Maximum output current allowed before current limiting occurs.

Values

Default:

Drive Rated Amps x 1.1

Min/Max:

0.0/Drive Rated Amps x 1.5 (Normal Duty); Drive Rated Amps x 1.8 (Heavy Duty)

Display:

0.1 A

PF 525

A486 [Shear Pin1 Level]

Related Parameter(s):

A487

,

A489

A488 [Shear Pin2 Level]

PowerFlex 525 only.

Sets the value of current at which the shear pin fault occurs after the time set in

A487

,

A489

[Shear Pin x Time]. Setting the value at 0.0 A disables this function.

Values

Default:

0.0 A (Disabled)

Min/Max:

0.0/(Drive Rated Amps x 2)

Display:

0.1 A

PF 525

A487 [Shear Pin 1 Time]

Related Parameter(s):

A486

,

A488

A489 [Shear Pin 2 Time]

PowerFlex 525 only.

Sets the continuous time the drive must be at or above the value set in

A486

,

A488

[Shear Pinx Level] before a shear pin fault occurs.

Values

Default:

0.00 s

Min/Max:

0.00/30.00 s

Display:

0.01 s

PF 525