Rockwell Automation Publication 520-UM001G-EN-E - September 2014

115

Programming and Parameters

Chapter 3

Advanced Program Group (continued)

A462 [PID 1 Integ Time]

Related Parameter(s):

A459

,

A471

A474 [PID 2 Integ Time]

PowerFlex 525 only.

Sets the value for the PID integral component when PID mode is enabled.

Values

Default:

2.0 s

Min/Max:

0.0/999.9 s

Display:

0.1 s

PF 525

A463 [PID 1 Diff Rate]

Related Parameter(s):

A459

,

A471

A475 [PID 2 Diff Rate]

PowerFlex 525 only.

Sets the value (in 1/second) for the PID differential component when PID mode is enabled.

Values

Default:

0.00

Min/Max:

0.00/99.99

Display:

0.01

PF 525

A464 [PID 1 Setpoint]

Related Parameter(s):

A459

,

A471

A476 [PID 2 Setpoint]

PowerFlex 525 only.

Provides an internal fixed value for process setpoint when PID mode is enabled.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

PF 525

A465 [PID 1 Deadband]

A477 [PID 2 Deadband]

PowerFlex 525 only.

Sets the lower limit of the PID output.

Values

Default:

0.0%

Min/Max:

0.0/10.0%

Display:

0.1%

PF 525

A466 [PID 1 Preload]

A478 [PID 2 Preload]

PowerFlex 525 only.

Sets the value used to preload the integral component on start or enable.

Values

Default:

0.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

PF 525

A467 [PID 1 Invert Err]

A479 [PID 2 Invert Err]

PowerFlex 525 only.

Changes the sign of the PID error.

Options

0 “Normal” (Default)

1 “Inverted”

PF 525