Rockwell Automation Publication 520-UM001G-EN-E - September 2014

71

Programming and Parameters

Chapter 3

Basic Display Group

b001 [Output Freq]

Related Parameter(s):

b002

,

b010

,

P043

,

P044

,

P048

,

P050

,

P052

Output frequency present at T1, T2 & T3 (U, V & W). Does not include slip frequency.

Values

Default:

Read Only

Min/Max:

0.00/[Maximum Freq]

Display:

0.01 Hz

b002 [Commanded Freq]

Related Parameter(s):

b001

,

b013

,

P043

,

P044

,

P048

,

P050

,

P052

Value of the active frequency command even if the drive is not running.

Values

Default:

Read Only

Min/Max:

0.00/[Maximum Freq]

Display:

0.01 Hz

IMPORTANT

The frequency command can come from a number of sources. See

Start and Speed Reference Control on page 46

for more information.

b003 [Output Current]

Output current present at T1, T2 & T3 (U, V & W).

Values

Default:

Read Only

Min/Max:

0.00/(Drive Rated Amps x 2)

Display:

0.01 A

b004 [Output Voltage]

Related Parameter(s):

P031

,

A530

,

A534

Output voltage present at T1, T2 & T3 (U, V & W).

Values

Default:

Read Only

Min/Max:

0.0/Drive Rated Volts

Display:

0.1V

b005 [DC Bus Voltage]

Filtered DC bus voltage level of the drive.

Values

Default:

Read Only

Min/Max:

0/1200VDC

Display:

1VDC

b006 [Drive Status]

Related Parameter(s):

A544

Present operating condition of the drive.

Values

Default:

Read Only

Min/Max:

00000/11111

Display:

00000

1 = True/Active, 0 = False/Inactive

Running

Digit 1

Forward

Digit 2

Accelerating

Digit 3

Decelerating

Digit 4

SafetyActive

(1)

Digit 5

(1)

Setting is specific to PowerFlex 525 drives only.