A459 [PID 1 Ref Sel]

A471 [PID 2 Ref Sel]

PowerFlex 525 only.

Stop drive before changing this parameter.

Selects the source of the PID reference.

Options

0 “PID Setpoint” (Default)

1 “Drive Pot”

2 “Keypad Freq”

3 “Serial/DSI”

4 “Network Opt”

5 “0-10V Input”

6 “4-20mA Input”

7 “Preset Freq”

8 “AnlgIn Multi”

(1)

9 “MOP Freq”

10 “Pulse Input”

11 “Step Logic”

(1)

12 “Encoder”

(1)

13 “EtherNet/IP”

(1)

(1) Setting is specific to PowerFlex 525 drives only.

PF 525

A460 [PID 1 Fdback Sel]

A472 [PID 2 Fdback Sel]

PowerFlex 525 only.

Selects the source of the PID feedback.

Options

0 “0-10V Input” (Default)

Note: PID does not function with bipolar input. Negative voltages are ignored and treated as zero.

1 “4-20mA Input”

2 “Serial/DSI”

3 “Network Opt”

4 “Pulse Input”

5 “Encoder”

(1)

6 “EtherNet/IP”

(1)

(1) Setting is specific to PowerFlex 525 drives only.

PF 525

A461 [PID 1 Prop Gain]

Related Parameter(s):

A459

,

A471

A473 [PID 2 Prop Gain]

PowerFlex 525 only.

Sets the value for the PID proportional component when the PID mode is enabled.

Values

Default:

0.01

Min/Max:

0.00/99.99

Display:

0.01

PF 525