Trim control – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 216

Advertising
background image

216

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Appendix F

PID Set Up

The Desired System Pressure set point is maintained as valves in the system
are opened and closed causing changes in flow.

When the PID Control Loop is disabled, the Commanded Speed is the
Ramped Speed Reference.

Trim Control

In Trim Control, the PID Output is added to the Speed Reference. In Trim
mode, the output of the PID loop bypasses the accel/decel ramp as shown. Trim
Control is used when

A458

or

A470

[PID x Trim Sel] is set to any option other

than 0.

Example

In a winder application, the PID Reference equals the Equilibrium set
point.

The Dancer Pot signal provides PID Feedback to the drive. Fluctuations in
tension result in a PID Error value.

The Master Speed Reference sets the wind/unwind speed.

Pump

PID Feedback =

Pressure Transducer Signal

PID Reference =

Desired System Pressure

Esc

Sel

+

PID Prop Gain

PID Loop

PID Integ Time

PID Diff Rate

PID Selected

[Speed Referencex]

PID Fdbk

PID Ref

PID

Error

+

+

+

+

PID

Output

Output

Freq

+

Accel/Decel

Ramp