Motor does not Start.

Drive does not Start from Start or Run Inputs wired to the terminal
block.

Cause(s)

Indication

Corrective Action

No output voltage to the motor.

None

Check the power circuit.
Check the supply voltage.
Check all fuses and disconnects.
Check the motor.
Verify that the motor is connected properly.
Check the control input signals.
Verify that a Start signal is present. If 2-Wire control is used, verify that either the Run

Forward or Run Reverse signal is active, but not both.

Verify that I/O Terminal 01 is active.
Verify that

P046

,

P048

,

P050

[Start Source x] matches your configuration.

Verify that

A544

[Reverse Disable] is not prohibiting movement.

Verify that safety inputs (Safety 1 and Safety 2) are active.

Improper boost setting at initial start-up.

None

Set

A530

[Boost Select] to 2 “35.0, VT”.

Drive is Faulted

Flashing red status light

Clear fault.
Press Stop if

P045

[Stop Mode] is set to a value between “0” and “3”.

Cycle drive power.
Set

A551

[Fault Clear] to 1 “Reset Fault” or 2 “Clear Buffer”.

Cycle digital input if

t062

,

t063

,

t065

...

t068

[DigIn TermBlk xx] is set to

13 “Clear Fault”.

Incorrect programming.

P046

,

P048

,

P050

[Start Source x] is set incorrectly.

None

Check setting for

b012

[Control Source].

Incorrect input wiring.
See

page 42

for wiring examples.

2 wire control requires Run Forward, Run Reverse or Jog

input.

3 wire control requires Start and Stop inputs
Stop input is always required.

None

Wire inputs correctly and/or install jumper.
If the PowerFlex 525 Safe-Torque-Off function is used, verify that inputs are active.
If 2-wire or 3-wire mode is used, verify that

t062

[DigIn TermBlk 02] and

t063

[DigIn

TermBlk 03] are set properly.

Incorrect Sink/Source jumper setting.

None

Set switch to match wiring scheme.

Cause(s)

Indication

Corrective Action

Drive is Faulted

Flashing red status light

Clear fault.
Press Stop if

P045

[Stop Mode] is set to a value between “0” and “3”.

Cycle drive power.
Set

A551

[Fault Clear] to 1 “Reset Fault” or 2 “Clear Buffer”.

Cycle digital input if

t062

,

t063

,

t065

...

t068

[DigIn TermBlk xx] is set to

13 “Clear Fault”.

Incorrect programming.

P046

,

P048

,

P050

[Start Source x] is set incorrectly.

t062

,

t063

[DigIn TermBlk 02/03] is set incorrectly.

None

Check parameter settings.

Incorrect input wiring.
See

page 42

for wiring examples.

2 wire control requires Run Forward, Run Reverse or Jog

input.

3 wire control requires Start and Stop inputs
Stop input is always required.

None

Wire inputs correctly and/or install jumper.
If the PowerFlex 525 Safe-Torque-Off function is used, verify that inputs are active.

Incorrect Sink/Source jumper setting.

None

Set switch to match wiring scheme.