Appendix D

Velocity StepLogic, Basic Logic and Timer/Counter Functions

Digit 2 – Defines what logic must be met to jump to a step other than the very next step.

Setting

Description

Logic

0

Skip Step (jump immediately)

SKIP

1

Step based on the time programmed in the respective [Stp Logic Time x] parameter.

TIMED

2

Step if “Logic In 1” is active (logically true)

TRUE

3

Step if “Logic In 2” is active (logically true)

TRUE

4

Step if “Logic In 1” is not active (logically false)

FALSE

5

Step if “Logic In 2” is not active (logically false)

FALSE

6

Step if either “Logic In 1” or “Logic In 2” is active (logically true)

OR

7

Step if both “Logic In 1” and “Logic In 2” is active (logically true)

AND

8

Step if neither “Logic In 1” or “Logic In 2” is active (logically true)

NOR

9

Step if “Logic In 1” is active (logically true) and “Logic In 2” is not active (logically false)

XOR

A

Step if “Logic In2” is active (logically true) and “Logic In 1” is not active (logically false)

XOR

b

Step after [Stp Logic Time x] and “Logic In 1” is active (logically true)

TIMED AND

C

Step after [Stp Logic Time x] and “Logic In 2” is active (logically true)

TIMED AND

d

Step after [Stp Logic Time x] and “Logic In 1” is not active (logically false)

TIMED OR

E

Step after [Stp Logic Time x] and “Logic In 2” is not active (logically false)

TIMED OR

F

Do not step OR no “jump to”, so use Digit 0 logic

IGNORE

Digit 1 – Defines what logic must be met to jump to the very next step.

Setting

Description

Logic

0

Skip Step (jump immediately)

SKIP

1

Step based on the time programmed in the respective [Stp Logic Time x] parameter.

TIMED

2

Step if “Logic In 1” is active (logically true)

TRUE

3

Step if “Logic In 2” is active (logically true)

TRUE

4

Step if “Logic In 1” is not active (logically false)

FALSE

5

Step if “Logic In 2” is not active (logically false)

FALSE

6

Step if either “Logic In 1” or “Logic In 2” is active (logically true)

OR

7

Step if both “Logic In 1” and “Logic In 2” is active (logically true)

AND

8

Step if neither “Logic In 1” or “Logic In 2” is active (logically true)

NOR

9

Step if “Logic In 1” is active (logically true) and “Logic In 2” is not active (logically false)

XOR

A

Step if “Logic In 2” is active (logically true) and “Logic In 1” is not active (logically false)

XOR

b

Step after [Stp Logic Time x] and “Logic In 1” is active (logically true)

TIMED AND

C

Step after [Stp Logic Time x] and “Logic In 2” is active (logically true)

TIMED AND

d

Step after [Stp Logic Time x] and “Logic In 1” is not active (logically false)

TIMED OR

E

Step after [Stp Logic Time x] and “Logic In 2” is not active (logically false)

TIMED OR

F

Use logic programmed in Digit 1

IGNORE