Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 40

Advertising
background image

40

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 1

Installation/Wiring

Control I/O Wiring Block Diagram Notes

(1) See

Digital Input Selection for Start Source on page 47

for more information on configuring the digital inputs.

(2) Two wire control shown. For three wire control use a momentary input

on I/O Terminal 02 to command a start. Use a

maintained input

for I/O Terminal 03 to change direction.

(3) When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as shown, to prevent

damage to the output.

IMPORTANT

I/O Terminal 01 is always a stop input. The stopping mode is determined by the
drive setting. See the tables below for more information.

Start Method

Stop Method

P046, P048, P050 [Start Source x]

I/O Terminal 01 Stop

Normal Stop

1 “Keypad”

Coast

Per P045
[Stop Mode]

2 “DigIn TrmBlk”

See

t062, t063 [DigIn TermBlk xx]

below

3 “Serial/DSI”

Coast

4 “Network Opt”

Coast

5 “EtherNet/IP”

Coast

Start Method

Stop Method

t062, t063 [DigIn TermBlk xx]

I/O Terminal 01 Stop

Normal Stop

48 “2-Wire FWD”

t064 [2-Wire Mode] is set to:
0, 1, or 2 = Coast
3 = per P045 [Stop Mode]

Per P045
[Stop Mode]

49 “3-Wire Start”

Per P045 [Stop Mode]

50 “2-Wire REV”

t064 [2-Wire Mode] is set to:
0, 1, or 2 = Coast
3 = per P045 [Stop Mode]

51 “3-Wire Dir”

Per P045 [Stop Mode]

IMPORTANT

The drive is shipped with a jumper installed between I/O Terminals 01 and 11.
Remove this jumper when using I/O Terminal 01 as a stop or enable input.

Control I/O Terminal Designations

No. Signal

Default

Description

Parameter

R1 Relay 1 N.O.

Fault

Normally open contact for output relay.

t076

R2 Relay 1 Common Fault

Common for output relay.

R5 Relay 2 Common Motor Running Common for output relay.

t081

R6 Relay 2 N.C.

Motor Running Normally closed contact for output relay.

01

Stop

Coast

Three wire stop. However, it functions as a stop under all input
modes and cannot be disabled.

P045

(1)

02

DigIn TermBlk 02/
Start/Run FWD

Run FWD

Used to initiate motion and also can be used as a programmable
digital input. It can be programmed with t062 [DigIn TermBlk
02] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.

P045

,

P046

,

P048

,

P050

,

A544

,

t062

03

DigIn TermBlk 03/
Dir/Run REV

Run REV

Used to initiate motion and also can be used as a programmable
digital input. It can be programmed with t063 [DigIn TermBlk
03] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.

t063

04

Digital Common

Return for digital I/O. Electrically isolated (along with the digital
I/O) from the rest of the drive.

05

DigIn TermBlk 05 Preset Freq

Program with t065 [DigIn TermBlk 05].
Current consumption is 6 mA.

t065