Debris protection, Storage, Derating guidelines for high altitude – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 1

Installation/Wiring

Derating Guidelines for High Altitude

The drive can be used without derating at a maximum altitude of
1000 m (3300 ft). If the drive is used above 1000 m (3300 ft):

Derate the maximum ambient temperature by 5

°C (9 °F) for every

additional 1000 m (3300 ft), subject to limits listed in the

Altitude Limit

(Based on Voltage)

table below.

Or

Derate the output current by 10% for every additional 1000 m (3300 ft),
up to 3000 m (9900 ft), subject to limits listed in the

Altitude Limit

(Based on Voltage)

table below.

High Altitude

Debris Protection

Take precautions to prevent debris from falling through the vents of the drive
housing during installation.

Storage

Store within an ambient temperature range of -40...85

°C

(1)

.

Store within a relative humidity range of 0...95%, noncondensing.

Do not expose to a corrosive atmosphere.

(1) The maximum ambient temperature for storing a Frame E drive is 70

°C.

Altitude Limit (Based on Voltage)

Drive Rating

Center Ground (Wye Neutral)

Corner Ground, Impedance
Ground, or Ungrounded

100...120V 1-Phase

6000 m

6000 m

200...240V 1-Phase

2000 m

2000 m

200...240V 3-Phase

6000 m

2000 m

380...480V 3-Phase

4000 m

2000 m

525...600V 3-Phase

2000 m

2000 m

Altitude (m)

Percentage of Rated Current (%)

40

90

100

110

120

80

70

60

50

0

4000

3000

2000

1000

Altitude (m)

Ambient Temperature (°C)

20

50

60

40

30

0

4000

3000

2000

1000

Advertising
This manual is related to the following products: