Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Appendix C

RS485 (DSI) Protocol

Reading (03) Drive
Operational Values

The PowerFlex 520-series Drive Operational Values can be read through the
network by sending Function Code 03 reads to register addresses
2102H...210AH.

Reading (03) and Writing
(06) Drive Parameters

To access drive parameters, the Modbus register address equals the parameter
number. For example, a decimal “1” is used to address Parameter b001 [Output
Freq] and decimal “41” is used to address Parameter P041 [Accel Time 1].

Additional Information

See

http://www.ab.com/drives/

for additional information.

2101H (8449)

125

Flash Update Required

126

Non Recoverable Error

127

DSI Flash Update Required

Drive Error Codes

Logic Status

Address (Decimal)

Value (Decimal)

Description

Drive Operational Values

Reference

Address (Decimal)

Description

2102H (8450)

Frequency Command (xxx.xx Hz)

2103H (8451)

Output Frequency (xxx.xx Hz)

2104H (8452)

Output Current (xxx.xx A)

2105H (8453)

DC-BUS Voltage (xxxV)

2106H (8454)

Output Voltage (xxx.xV)