A444 [Accel Time 3]
A446 [Accel Time 4]

Sets the rate of acceleration for all speed increases when selected by digital inputs.

Values

Default:

10.00 s

Min/Max:

0.00/600.00 s

Display:

0.01 s

A445 [Decel Time 3]
A447 [Decel Time 4]

Sets the rate of deceleration for all speed decreases when selected by digital inputs.

Values

Default:

10.00 s

Min/Max:

0.00/600.00 s

Display:

0.01 s

A448 [Skip Frequency 1]

Related Parameter(s):

A449

,

A451

,

A453

,

A455

A450 [Skip Frequency 2]

A452 [Skip Frequency 3]
A454 [Skip Frequency 4]

PowerFlex 525 only.

Works in conjunction with

A449

,

A451

,

A453

and

A455

[Skip Freq Band x] creating a range of frequencies at which the drive does not operate continuously.

Values

Default:

0.0 Hz (Disabled)

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

PF 525

A449 [Skip Freq Band 1]

Related Parameter(s):

A448

,

A450

,

A452

,

A454

A451 [Skip Freq Band 2]

A453 [Skip Freq Band 3]
A455 [Skip Freq Band 4]

PowerFlex 525 only.

Determines the band around

A448

,

A450

,

A452

and

A454

[Skip Frequency x].

Values

Default:

0.0 Hz

Min/Max:

0.0/30.0 Hz

Display:

0.1 Hz

PF 525

Frequency

Time

Skip Frequency

Command

Frequency

Drive Output

Frequency

2x Skip

Frequency Band

Advertising