C121 [Comm Write Mode]

Saves parameter values in active drive memory (RAM) or in drive non-volatile memory (EEPROM).

Options

0 “Save” (Default)

1 “RAM only”

IMPORTANT

Parameter values set prior to setting 1 “RAM only” are saved in RAM.

ATTENTION: If Automatic Drive Configuration (ADC) is used, this parameter must remain at its default value of 0 “Save”.

C122 [Cmd Stat Select]

PowerFlex 525 only.

Selects velocity-specific or position/fibers-specific Command and Status Word bit definitions for use over a communication network. See

Writing (06) Logic Command Data on page 191

for more information. This parameter cannot be changed when an I/O connection is established through the communication adapter or the drive’s embedded EtherNet/IP port.

Options

0 “Velocity” (Default)

1 “Position”

PF 525

C123 [RS485 Data Rate]

Sets the communications baud rate (bits/second) for the RS485 port. A reset or power cycle is required after selection is made.

Options

0 “1200”

1 “2400”

2 “4800”

3 “9600” (Default)

4 “19,200”

5 “38,400”

C124 [RS485 Node Addr]

Sets the Modbus drive node number (address) for the RS485 port if using a network connection. A reset or power cycle is required after selection is made.

Values

Default:

100

Min/Max:

1/247

Display:

1

C125 [Comm Loss Action]

Related Parameter(s):

P045

Sets the drive's response to a loss of connection or excessive communication errors on the RS485 port.

Options

0 “Fault” (Default)

1 “Coast Stop”

Stops drive using “Coast to stop”.

2 “Stop”

Stops drive using

P045

[Stop Mode] setting.

3 “Continu Last”

Drive continues operating at communication commanded speed saved in RAM.

C126 [Comm Loss Time]

Related Parameter(s):

C125

Sets the time that the drive remains in communication loss with the RS485 port before taking the action specified in

C125

[Comm Loss Action]. See

Appendix C

for more information.

Values

Default:

5.0 s

Min/Max:

0.1/60.0 s

Display:

0.1 s

IMPORTANT

This setting is effective only if I/O that controls the drive is transmitted through the RS485 port.