Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 126
![background image](/manuals/579250/126/background.png)
84
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Chapter 5 Using the LCD
10. You can identify this change of data value is reflected to your RSLogix
500/RSLogix Micro programming software.
11. Now, we will view an example of the data value of a protected property. If
LCD Edit Disable is set to checked (enable), the "Protected!" message will
be displayed and this data file cannot be edited by the LCD.
12. Try to move the cursor to the data value position by pressing the OK key.
Because this double integer file is protected, you will find that the cursor
even does not move to the data value position.
TIP
After changing the data value of a target double word, press the OK
key to apply the changes or press the ESC key to discard the changes.