Specifications Appendix A

Specifications for Outputs in Hazardous Locations
(Class 1, Division 2, Groups A, B, C, D)

Relay Outputs

Description

1766-L32AWA/A,
1766-L32BWA/A

1766-L32BXB/A

Maximum controlled load

1440 VA

1080 VA

Maximum Continuous Current:

Current per channel and group
common

2.5 A per channel
8A max channel 8...11
common

2.5 A per channel

Current per
controller

at 150V max

28 A or total of per-point
loads, whichever is less

at 240V max

20 A or total of per-point
loads, whichever is less

Relay Outputs

Description

1766-L32AWA/A, 1766-L32BWA/A, 1766-L32BXB/A

Turn On Time/Turn Off Time

10 msec (maximum)

(1)

(1)

Scan time dependent

Load current

10 mA (minimum)

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

240V AC

7.5 A

0.75 A

2.5 A

1800 VA

180 VA

120V AC

15.0 A

1.5 A

2.5 A

1800 VA

180 VA

250V DC

0.11 A

1.0 A

28 VA

125V DC

0.22 A

1.0 A

28 VA

Advertising