Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 4 Communication Connections

When cutting cable segments, make them long enough to route them from one
AIC+ to the next, with sufficient slack to prevent strain on the connector. Allow
enough extra cable to prevent chafing and kinking in the cable.

Use these instructions for wiring the Belden #3106A or #9842 cable. (See Cable
Selection Guide on page 77
if you are using standard Allen-Bradley cables.)

Connecting the Communication Cable to the DH-485 Connector

Single Cable Connection

When connecting a single cable to the DH-485 connector, use the following
diagram.

TIP

A daisy-chained network is recommended. Do not make the incorrect
connection shown below:

Belden #3106A
or #9842

Belden #3106A or
#9842

Belden #3106A or
#9842

Connector

Connector

Connector

Incorrect

Orange with White Stripes

White with Orange Stripes

Shrink Tubing Recommended

Blue (#3106A) or
Blue with White
Stripes (#9842)

Drain Wire

6 Termination

5 A
4 B

3 Common

2 Shield
1 Chassis Ground