Default Communication
Configuration

The MicroLogix 1400 communication Channel 0 has the following default
communication configuration.

See Chapter 5 for more information about using the LCD Display.

See Appendix E for more information about communicating.

Using the Communications
Toggle Functionality

The Communications Toggle Functionality can be operated using the LCD
display on the controller, as shown below.

Use the Communications Toggle Functionality to change from the user-defined
communication configuration to the default communications mode and back on
Channel 0. The Default Communications (DCOMM) indicator on the LCD
display operates to show when the controller is in the default communications

TIP

For Channel 0, the default configuration is present when:

• The controller is powered-up for the first time.

• The communications toggle functionality specifies default

communications (specified using the LCD Display. The DCOMM
indicator on the LCD Display is on, that is, lit in solid rectangle).

• An OS upgrade is completed.

DF1 Full-Duplex Default Configuration Parameters

Parameter

Default

Baud Rate

19.2 KBps

Parity

none

Source ID (Node Address)

1

Control Line

no handshaking

Error Detection

CRC

Embedded Responses

auto detect

Duplicate Packet (Message) Detect

enabled

ACK Timeout

50 counts

NAK retries

3 retries

ENQ retries

3 retries

Stop Bits

1

Data Bits

8