C - troubleshooting your system, Understanding the controller status indicators, Controller status led indicators – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 197: Troubleshooting your system, Appendix

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

157

Appendix

C

Troubleshooting Your System

This chapter describes how to troubleshoot your controller. Topics include:

• understanding the controller status indicators
• controller error recovery model
• analog expansion I/O diagnostics and troubleshooting
• calling Rockwell Automation for assistance

Understanding the
Controller Status Indicators

The MicroLogix 1400 provides three groups of status indicators:

• the status LEDs on the top of the controller,
• the status indicators on the LCD
• the I/O status indicators on the LCD.

Together they provide a mechanism to determine the current status of the
controller if a programming device is not present or available.

Controller Status LED Indicators

Figure 3 - Controller LED Location

Controller LED Indicators

LED

Color

Indicates

POWER

off

No input power, or power error condition

green

Power on

RUN

off

Not executing the user program

green

Executing the user program in run mode

green flashing

Memory module transfer occurring

POWER

RUN

FAULT

FORCE

1400

44607

Advertising