130

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix A Specifications

Specifications for Outputs in (Non-Hazardous) Locations only

Figure 1 - MicroLogix 1400 DC Input Power Requirements for 1766-L32BXB/A Unit

Relay Outputs

Description

1766-L32AWA/A,
1766-L32BWA/A

1766-L32BXB/A

Maximum controlled load

1440 VA

1080 VA

Maximum Continuous Current:

Current per channel and group
common

2.5 A per channel
8A max channel 8...11
common

2.5 A per channel

Current per
controller

at 150V max

28 A or total of per-point
loads, whichever is less

at 240V max

20 A or total of per-point
loads, whichever is less

Relay Outputs

Description

1766-L32AWA/A, 1766-L32BWA/A, 1766-L32BXB/A

Turn On Time/Turn Off Time

10 msec (maximum)

(1)

(1)

Scan time dependent

Load current

10 mA (minimum)

4

8

12

16

20

28

21

14

7

1766-L32BXB/A Typical Power Requirements