General Specifications

Specification

1762-IF2OF2

1762-IF4

1762-OF4

1762-IR4

1762-IT4

Shipping weight,
approx.
(with carton)

240 g (0.53 lbs.)

235 g (0.517 lbs.)

260 g (0.57 lbs.)

220 g (0.53 lbs.)

Bus current draw, max.

40 mA at 5V DC
105 mA at 24V DC

40 mA at 5V DC
50 mA at 24V DC

40 mA at 5V DC
165 mA at 24V DC

40 mA at 5V DC
50 mA at 24V DC

40 mA at 5V DC
50 mA at 24V DC

Analog normal
operating range

Voltage: 0…10V DC
Current: 4…20 mA

Voltage: -10…+10V DC
Current: 4…20 mA

Voltage 0…10V DC
Current: 4…20 mA

NA

NA

Full scale

(1)

analog

ranges

Voltage: 0…10.5V DC
Current: 0…21 mA

Voltage:
-10.5…+10.5V DC
Current: -21…+21 mA

Voltage:
0…10.5V DC
Current: 0…21 mA

NA

NA

Resolution

12 bits (unipolar)

15 bits (bipolar)

(4)

12 bits (unipolar)

Input filter and
configuration
dependent

15 bits plus sign

Repeatability

(2)

±0.12%

(4)

±0.12%

(4)

±0.12%

(4)

±0.1 °C (±0.18 °F) for
Ni and NiFe
±0.2 °C
(±0.36 °F)…±0.2 °C
(±0.36 °F) for other RTD
inputs
±0.04 ohm for 150 ohm
resistances
±0.2 ohm for other
resistances

See Table 146

Input and output group
to system isolation

30V AC/30V DC rated working voltage

(3)

(N.E.C. Class 2 required)
(IEC Class 2 reinforced insulation)
type test: 500V AC or 707V DC for 1 minute

30V AC/30V DC rated
working voltage
(IEC Class 2 reinforced
insulation)
type test: 500V AC or
707V DC for 1 minute

30V AC/30V DC
working voltage
type test: 500V AC or
707V DC for 1 minute

30V AC/30V DC
working voltage
qualification test: 720V
DC for 1 minute

Vendor I.D. code

1

1

1

1

1

Product type code

10

10

10

10

10

Product code

75

67

66

65

64

(1) The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to convert the analog input up to the maximum

full scale range.

(2) Repeatability is the ability of the module to register the same reading in successive measurements for the same signal.

(3) Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth ground.

(4) Only applicable to Series B I/O modeles.

Input Specifications

Specification

1762-IF2OF2

1762-IF4

1762-IR4

1762-IT4

Number of inputs

2 differential (unipolar)

4 differential (bipolar)

4

4 input channels plus 1 CJC
sensor

Update time (typical)

2.5 ms

130, 250, 290, 450, 530 ms
(selectable)

Input filter and cofiguration
dependent

NA

A/D converter type

Successive approximation

Successive approximation

Delta-Sigma

Delta-Sigma

Common mode voltage
range

(1)

±27V ±27V NA

±10V