Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 347

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

307

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

60

Application Layer Error Codes:
0: NO_ERROR - No error found in the Application Layer.
1: FC_CANNOT_BROADCAST - Reserved
2: FC_NOT_SUPPORTED - The received packet has unsupported
Function Code.
3: OBJ_NOT_SUPPORTED - The received packet has unsupported
object(s).
4: BAD_REQUEST_LENGTH - Reserved
5: CONFIGURATION_ERROR - The error was caused by the invalid
configuration during packet generating. E.g. invalid Data Set
Configuration.
6: BAD_PARAMETER - The received packet has invalid parameters
except Function Code and Object Codes. E.g. invalid Qualifier codes.
7: BAD_FILE_TYPE - The error was caused by invalid configuration in
DNP3 Slave Application Layer. Invalid File Type specified.
8: BAD_FILE_NUMBER - The error was caused by invalid
configuration in DNP3 Slave Application Layer. Invalid File Number
specified.
9: BAD_DNP3_ADDRESS - The error was caused by invalid
configuration in DNP3 Slave Application Layer. Invalid File Number
specified.
10: TABLE_WRITE_PROTECTED - The specified DNP3 object data file
has been locked to be written.
11: TABLE_ACCESS_DENIED - The specified DNP3 object data file
has been locked to be read or written.
12: TABLE_OWNERSHIP_ERROR - The specified DNP3 object data
file has been locked to be read or written.
If an error code is within 6 to 12, related file number and element
number are shown in word 64 and 65.

DNP3 Slave - Application Layer Diagnostics for DNP3
Slave.

61

Application Layer Error Count

62

Function Code that caused the last error

63

Last Transmitted IIN in the response

64

Data file number of last error request

65

Data element number of last error request

66

Received Confirm Function Code Counter

67

Received Read Function Code Counter

68

Received Write Function Code Counter

69

Received Function Code Counter other than Confirm, Read and Write
Function Codes.

70

Transmitted Solicited Response Function Code Counter

71

Transmitted Unsolicited Response Function Code Counter

72

Number of events to be reported.

Data File for Troubleshooting