Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

323

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

41

1

Analog Output - 32-bit

3 (select)
4 (operate)
5 (direct op)
6 (dir. op, no ack)

17, 27, 28 (index)

129 (response)

echo of request

41

2

Analog Output - 16-bit

3 (select)
4 (operate)
5 (direct op)
6 (dir. op, no ack)

17, 27, 28 (index)

129 (response)

echo of request

41

3

Analog Output - Single-prec
flt-pt

3 (select)
4 (operate)
5 (direct op)
6 (dir. op, no ack)

17, 27, 28 (index)

129 (response)

echo of request

50

1

Time and Date - Absolute time

1 (read)

07 (limited qty = 1)

129 (response)

07 (limited qty)
(qty = 1)

2 (write)

07 (limited qty = 1)

50

3

Time and Date - Absolute time
at last recorded time

2 (write)

07 (limited qty = 1)

51

1

Time and Date CTO - Absolute
time, synchronized

129 (response)
130 (unsol. resp)

07 (limited qty)
(qty = 1)

51

2

Time and Date CTO - Absolute
time, unsynchronized

129 (response)
130 (unsol. resp)

07 (limited qty)
(qty = 1)

52

2

Time Delay - Fine

129 (response)

07 (limited qty)
(qty = 1)

60

1

Class Objects - Class 0 data

1 (read)

06 (no range, or all)

60

2

Class Objects - Class 1 data

1 (read)

06 (no range, or all)
07, 08 (limited qty)

20 (enbl. unsol.)
21 (dab. unsol.)

06 (no range, or all)

60

3

Class Objects - Class 2 data

1 (read)

06 (no range, or all)
07, 08 (limited qty)

60

4

Class Objects - Class 3 data

1 (read)

06 (no range, or all)
07, 08 (limited qty)

20 (enbl. unsol.)
21 (dab. unsol.)

06 (no range, or all)

70

2

File-Control - authentication

29 (authenticate file)

5B (free format)

129 (response)

5B (free format)

70

3

File Control - file command

25 (open file)

5B (free format)

70

3

File Control - file command

27 (delete file)

5B (free format)

70

4

File Control - file command
status

26 (close file)

5B (free format)

129 (response)

5B (free format)

70

4

File Control - file command
status

30 (abort file)

5B (free format)

129 (response)

5B (free format)

70

5

File Control - file transport

1 (read file)

5B (free format)

129 (response)

5B (free format)

70

5

File Control - file transport

2 (write file)

5B (free format)

129 (response)

5B (free format)

70

6

File Control - file transport
status

129 (response)

5B (free format)

Implementation Table for Series B controllers

DNP Object Group & Variation

Request
DNP3 Master may issue
MicroLogix 1400 must parse

Response
DNP3 Master must parse
MicroLogix 1400 may issue

Group
Num

Var Num Description

Function Codes
(dec)

Qualifier Codes (hex)

Function Codes
(dec)

Qualifier Codes
(hex)