Wire Your Controller Chapter 3

Figure 31 - 1762-IF4 Terminal Block Layout

Figure 32 - Differential Sensor Transmitter Types

TIP

Grounding the cable shield at the module end only usually provides
sufficient noise immunity. However, for best cable shield
performance, earth ground the shield at both ends, using a 0.01µF
capacitor at one end to block AC power ground currents, if necessary.

IN 1 (+)

IN 0 (+)

IN 1 (-)

IN 0 (-)

IN 3 (+)

IN 2 (+)

IN 3 (-)

IN 2 (-)

COM

COM

Commons internally connected.

IN 0 (+)

IN 0 (-)

IN 3 (+)

IN 3 (-)

IN 2 (+)

IN 2 (-)

COM

IN 1 (-)

IN 1 (+)

COM

Analog Sensor