Dnp3 data files – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 276

Advertising
background image

236

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)

DNP3 Data Files

Basically, the index number of DNP objects of each type is evaluated by the
firmware automatically per the number of elements. For example, if a Binary
Input object file was configured as an element, the highest index number of the
Binary Input object is 15. The index number can only be increased by 16. If a
Double-Bit Binary Input object file was configured as an element, the highest
index number of the Double-Bit Binary Input object is 7. The index number can
only be increased by 8.

As another example, if a 16-bit Analog Input object file was configured as an
element, the highest index number is 1. Except for Binary and Double-Bit Binary
type objects, the index number can be increased by 1.

Relationship between DNP3 object database and MicroLogix data files

DNP Objects

Micrologix Data Files

Object Name

Related
Groups

Maximum
Configurable
Index

File name for Data

File Type

File
Number

Maximum
Configurable
Elements

Binary Input Object

1, 2

4096

Binary Input Object File

Only B file

3, 9 to 255

256

Double Bit Binary Input
Object

3, 4

2048

Double Bit Binary Input Object File

Only B file

3, 9 to 255

256

Binary Output Object

10, 12

4096

Binary Input Object File

Only B file

3, 9 to 255

256

Counter Object

20, 22

256

16-bit Counter Object File

Only N file

7, 9 to 255

256

32 bit Counter Object File

Only L file

9 to 255

Frozen Counter Object

21, 23

reflection of
Counter Object
which was
configured

reflection of 16-bit Counter Object File

-

-

-

reflection of 32-bit Counter Object File

Analog Input Object

30, 32

256

16-bit Analog Input Object File

Only N file

7, 9 to 255

256

32-bit Analog Input Object File

Only L file

9 to 255

Short Floating Point Analog Input Object File Only F file

8, 9 to 255

Analog Output Object

40, 41

256

16-bit Analog Output Object File

Only N file

256

32-bit Analog Output Object File

Only L file

9 to 255

Short Floating Point Analog Output Object
File

Only F file

8, 9 to 255

BCD Object

101

256

Small BCD Object File

Only N file

7, 9 to 255

256

Data Set Object(In
Series B)

85, 87, 88

10

Data Set Prototypes Object File

Only N file

7, 9 to 255

10

86, 87, 88

Data Set Descriptors Object File

Advertising
This manual is related to the following products: