Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 3 Wire Your Controller

used. See for recommended suppressors. As shown below, these surge
suppression circuits connect directly across the load device.

Suitable surge suppression methods for inductive AC load devices include a
varistor, an RC network, or an Allen-Bradley surge suppressor, all shown below.
These components must be appropriately rated to suppress the switching
transient characteristic of the particular inductive device. See Recommended
Surge Suppressors on page 30
for recommended suppressors.

Recommended Surge Suppressors

Use the Allen-Bradley surge suppressors shown in the following table for use with
relays, contactors, and starters.

+24V DC

IN4004 Diode

Relay or Solid
State DC Outputs

24V DC common

VAC/DC

Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
COM

(A surge suppressor
can also be used.)

Surge Suppression for Inductive AC Load Devices

Output Device

Output Device

Output Device

Varistor

RC Network

Surge
Suppressor

Recommended Surge Suppressors

Device

Coil Voltage

Suppressor Catalog Number

Type

(4)

Bulletin 100/104K 700K

24…48V AC

100-KFSC50

RC

110…280V AC

100-KFSC280

380…480V AC

100-KFSC480

12…55 V AC, 12…77V DC

100-KFSV55

MOV

56…136 VAC, 78…180V DC

100-KFSV136

137…277V AC, 181…250 V DC

100-KFSV277

12…250V DC

100-KFSD250

Diode

Advertising