Module error field, Extended error information field, Hardware errors – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 204: Configuration errors, Error codes

Advertising
background image

164

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix C Troubleshooting Your System

Module Error Field

The purpose of the module error field is to classify module errors into three
distinct groups, as described in the table below. The type of error determines what
kind of information exists in the extended error information field. These types of
module errors are typically reported in the controller’s I/O status file. Refer to the

MicroLogix 1400 Programmable Controllers Instruction Set Reference Manual,
publication

1766-RM001

for more information.

.

Extended Error Information Field

Check the extended error information field when a non-zero value is present in
the module error field. See Extended Error Codes for 1762-IF2OF2 on page 164.

Hardware Errors

General or module-specific hardware errors are indicated by module error code 2.

Configuration Errors

If you set the fields in the configuration file to invalid or unsupported values, the
module ignores the invalid configuration, generates a non-critical error, and keeps
operating with the previous configuration.

The table below lists the configuration error codes defined for the module.

Error Codes

Module Error Types

Error Type

Module Error Field Value
Bits 11 through 09
(Binary)

Description

No Errors

000

No error is present. The extended error field holds no additional information.

Hardware Errors

001

General and specific hardware error codes are specified in the extended error information
field.

Configuration Errors

010

Module-specific error codes are indicated in the extended error field. These error codes
correspond to options that you can change directly. For example, the input range or input
filter selection.

TIP

If no errors are present in the module error field, the extended error
information field is set to zero.

Extended Error Codes for 1762-IF2OF2

Error Type

Hex Equivalent

(1)

Module Error
Code

Extended Error
Information Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state