Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)

Related Configuration File Number:

• Binary Output Config File Number

To generate a Binary Output Object from the DNP3 Subsystem in the controller,
you should configure Binary Output Object File Number in the DNP3 Slave
Application Layer Configuration file.

When the Binary Output Object File is configured, Index number starts from 0.
1 bit is used for 1 Index.

As an example, a Binary Output Object File is configured as shown below. This
file has 10 elements and 160 Binary Output points. Index 0 of the Binary Output
Object is B11:0/0, Index 1 is B11:0/1 and Index 159 is B11:9/15.

As an example, a Binary Output Config File shown below has 10 elements. Each
bit can be configured for Online information (if the corresponding point is active
or not, 0=offline, 1=online) of the Binary Output points. B31:0/0 is for Index 0,
B31:0/1 is for Index 1 and B31:9/15 is for Index 159. In the example below, all
bits are cleared and all of the points are in offline state.