Communication error during tftp transfer, Missing or corrupt os state – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 221

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

181

Using ControlFLASH to Upgrade Your Operating System Appendix D

To clear this error:

1. Connect the controller's Ethernet port directly to the computer’s Ethernet

port using a crossover cable, or disable or uninstall any firewall VPN or
virus protection software running on the computer.

2. Cycle power to the processor.
3. Restart the firmware upgrade procedure as described in the section Using

ControlFLASH for Firmware Upgrade on page 169.

Communication error during TFTP transfer

This error message is displayed when there is a communication error during
TFTP transfer.

To clear this error:

1. Check your Ethernet connections are intact.
2. Cycle power to the processor.
3. Restart the firmware upgrade procedure as described in the section Using

ControlFLASH for Firmware Upgrade on page 169

4. If the error still persists, connect the controller's Ethernet port directly to

the computer’s Ethernet port using a crossover cable, and then repeat from

step 2

.

Missing or Corrupt OS state

The Boot Firmware runs the controller in this state.

When the controller is in this state, the controller shows either one of the
following:

ATTENTION: Do not interrupt the flash procedure, once you have
begun to download the firmware. If the flash procedure is
interrupted the controller will be in a Missing or Corrupt OS state
on the next power up.