Chapter 3 Wire Your Controller

Sinking and Sourcing
Wiring Diagrams

Any of the MicroLogix 1400 DC embedded input groups can be configured as
sinking or sourcing depending on how the DC COM is wired on the group.

1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA,
1766-L32AWAA, 1766-L32BXBA Wiring Diagrams

Figure 6 - 1766-L32AWA/L32AWAA Input Wiring Diagram

(1)

(1) “NOT USED” terminals are not intended for use as connection points.

Type

Definition

Sinking Input

The input energizes when high-level voltage is applied to the input terminal
(active high). Connect the power supply VDC (-) to the input group’s COM
terminal.

Sourcing Input

The input energizes when low-level voltage is applied to the input terminal
(active low). Connect the power supply VDC (+) to the input group’s COM
terminal.

ATTENTION: The 24V DC sensor power source must not be used
to power output circuits. It should only be used to power input
devices (for example. sensors, switches). See Master Control Relay
on page 13
for information on MCR wiring in output circuits.

TIP

In the following diagrams, lower case alphabetic subscripts are
appended to common-terminal connections to indicate that different
power sources may be used for different isolated groups, if desired.

NOT

USED

NOT

USED

COM 0

L2a

L1a

IN0

IN1

IN2

IN3

COM 1

L2b

L1b

IN4

IN5

IN6

IN7

COM 2

L2c

L1c

IN8

IN9

IN10

IN11

COM 3

L2d

L1d

IN12

IN13

IN14

IN15

IN17

IN18

IN19

IN16

COM

ANA

A

GND

A

IN0

IV0(+)

IV1(+)

IV2(+)

IV3(+)

A

IN1

A

IN2

A

IN3

1766-L32AWAA only