Recommended user-supplied components – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 94

Advertising
background image

80

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 4 Communication Connections

Recommended User-Supplied Components

These components can be purchased from your local electronics supplier.

User Supplied Components

Component

Recommended Model

external power supply and chassis ground

power supply rated for 20.4...28.8V dc

NULL modem adapter

standard AT

straight 9-25 pin RS-232 cable

see table below for port information if making
own cables

1761-CBL-AP00 or 1761-CBL-PM02

DB-9 RS-232

RS-485 connector

cable straight D connector

Port 1

Port 2

Port 3

6

7

8

9

1

2

3
4

5

4

1 2

5

6

7

8

3

6

5

4

3

2
1

Pin Port 1: DB-9 RS-232

Port 2

(2)

: (1761-CBL-PM02

cable)

Port 3: RS-485
Connector

1

received line signal detector
(DCD)

24V dc

chassis ground

2

received data (RxD)

ground (GND)

cable shield

3

transmitted data (TxD)

request to send (RTS)

signal ground

4

DTE ready (DTR)

(1)

received data (RxD)

(3)

DH-485 data B

5

signal common (GND)

received line signal detector
(DCD)

DH-485 data A

6

DCE ready (DSR)

(1)

clear to send (CTS)

(3)

termination

7

request to send (RTS)

transmitted data (TxD)

not applicable

8

clear to send (CTS)

ground (GND)

not applicable

9

not applicable

not applicable

not applicable

(1)

On port 1, pin 4 is electronically jumpered to pin 6. Whenever the AIC+ is powered on, pin 4 will match the
state of pin 6.

(2)

An 8-pin mini DIN connector is used for making connections to port 2. This connector is not commercially
available. If you are making a cable to connect to port 2, you must configure your cable to connect to the
Allen-Bradley cable shown above.

(3)

In the 1761-CBL-PM02 cable, pins 4 and 6 are jumpered together within the DB-9 connector.

Advertising