Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

139

Specifications Appendix A

Output group to output
group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. code

1

Product type code

7

Product code

120

121

124

98

(1) Only applicable to Series B I/O modules.

Output Specifications

Specification

1762-OW8

1762-OW16

1762-OX6I

1762-IQ8OW6

Relay Contact Ratings (1762-OW8, 1762-OW16, and 1762-IQ8OW6)

Maximum Volts

Amperes
Continuous

Amperes

Volt-Amperes

Make

Break

Make

Break

240V AC

2.5A

(1)

(1) 1.5A above 40 °C (104 °F).

7.5A

0.75A

1800 VA

180 VA

120V AC

2.5A

(2)

15A

1.5A

1800 VA

180 VA

125V DC

1.0A

0.22A

(2)

(2) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28

VA by the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V,
the make/break ratings for relay contacts cannot exceed 2A.

28 VA

24V DC

2.0A

1.2A

(3)

Relay Contact Ratings 1762-OX6I

Volts (max.)

Continuous
Amps per
Point
(max.)

(1)

(1) The continuous current per module must be limited so the module power does not exceed 1440VA.

Amperes

(3)

(3) Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of

the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.

Voltamperes

Make

Break

Make

Break

240V AC

5.0 A

15 A

1.5 A

3600 VA

360 VA

120V AC

7.0 A

(2)

(2) 6 A in ambient temperatures above 40 °C (104.°F)

30 A

3.0 A

125V DC

2.5 A

0.4 A

50 VA

(4)

(4) DC Make/Break Voltamperes must be limited to 50 VA for DC voltages between 28V DC and 125V DC. DC

Make/Break Voltamperes below 28V DC are limited by the 7 A Make/Break current limit.

24V DC

7.0 A

(2)

7.0 A

168 VA

(4)