Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 360

Advertising
background image

320

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)

0

255

Device Attributes - List of
attribute variations

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00 (start-stop)

1

0

Binary Input - Any Variation

1 (read)

00, 01 (start-stop)

06 (no range, or all)

1

1

Binary Input - Packed format

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00, 01 (start-stop)

1

2

Binary Input - With flags

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00, 01 (start-stop)

2

0

Binary Input Event - Any
Variation

1 (read)

06 (no range, or all)
07, 08 (limited qty)

2

1

Binary Input Event - Without
time

1 (read)

06 (no range, or all)
07, 08 (limited qty)

129 (response)
130 (unsol. resp)

17, 28 (index)

2

2

Binary Input Event - With
absolute time

1 (read)

06 (no range, or all)
07, 08 (limited qty)

129 (response)
130 (unsol. resp)

17, 28 (index)

2

3

Binary Input Event - With
relative time

1 (read)

06 (no range, or all)
07, 08 (limited qty)

129 (response)
130 (unsol. resp)

17, 28 (index)

3

0

Double-bit Binary Input - Any
Variation

1 (read)

00, 01 (start-stop)
06 (no range, or all)

3

1

Double-bit Binary Input - Packed
format

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00, 01 (start-stop)

3

2

Double-bit Binary Input - With
flags

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00, 01 (start-stop)

4

0

Double-bit Binary Input Event -
Any Variation

1 (read)

06 (no range, or all)
07, 08 (limited qty)

4

1

Double-bit Binary Input Event -
Without time

1 (read)

06 (no range, or all)
07, 08 (limited qty)

129 (response)
130 (unsol. resp)

17, 28 (index)

4

2

Double-bit Binary Input Event -
With absolute time

1 (read)

06 (no range, or all)
07, 08 (limited qty)

129 (response)
130 (unsol. resp)

17, 28 (index)

4

3

Double-bit Binary Input Event -
With relative time

1 (read)

06 (no range, or all)
07, 08 (limited qty)

129 (response)
130 (unsol. resp)

17, 28 (index)

10

0

Binary Output - Any Variation

1 (read)

00, 01 (start-stop)

06 (no range, or all)

10

2

Binary Output - Output status
with flags

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00, 01 (start-stop)

12

1

Binary Command - Control relay
output block (CROB)

3 (select)
4 (operate)
5 (direct op)
6 (dir. op, no ack)

17, 28 (index)

129 (response)

echo of request

20

0

Counter - Any Variation

1 (read)

00, 01 (start-stop)

06 (no range, or all)

20

1

Counter - 32-bit with flag

1 (read)

00, 01 (start-stop)
06 (no range, or all)

129 (response)

00, 01 (start-stop)

Implementation Table for Series B controllers

DNP Object Group & Variation

Request
DNP3 Master may issue
MicroLogix 1400 must parse

Response
DNP3 Master must parse
MicroLogix 1400 may issue

Group
Num

Var Num Description

Function Codes
(dec)

Qualifier Codes (hex)

Function Codes
(dec)

Qualifier Codes
(hex)

Advertising
This manual is related to the following products: