Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

239

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

ladder logic or communications, the MicroLogix 1400 clears it automatically
after generating an event at the end of scan. The bit DCE is used to suppress the
events by the change of state.

For example, if you want to trigger an event for an analog point every 15 minutes,
you should set the TE bit every 15 minutes by the ladder logic. But, in this case,
you may not want the state change events to be generated. Then, set the bit DCE.
You can get the timed events every 15 minutes.

Related Configuration File Number:

• 16-bit Counter Config File Number
• 32-bit Counter Config File Number
• 16-bit Frozen Counter Config File Number
• 32-bit Frozen Counter Config File Number
• 16-bit Analog Input Config File Number
• 32-bit Analog Input Config File Number
• Short Floating Point Analog Input Config File Number

For Counter type data, you can configure Threshold information in the
Configuration file. Each element can be configured to the threshold value for
each point. A counter event is generated if the absolute value of the difference
between the present value of a counter point and the value that was most recently
queued as an event for that point exceeds the threshold value that was configured
in this file.

Related Configuration File Numbers:

• 16-bit Counter Threshold Config File Number (In Series B)

Class and Object Configuration for Other Input Data Type

Bit Offset

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Element 0

F7

F6

F5

F4

F3

F2

F1

F0

r

r

DCE

TE

r

r

C1

C0

Element 1

F7

F6

F5

F4

F3

F2

F1

F0

r

r

DCE

TE

r

r

C1

C0

Element 2

F7

F6

F5

F4

F3

F2

F1

F0

r

r

DCE

TE

r

r

C1

C0

Element 3

F7

F6

F5

F4

F3

F2

F1

F0

r

r

DCE

TE

r

r

C1

C0

Element 4

F7

F6

F5

F4

F3

F2

F1

F0

r

r

DCE

TE

r

r

C1

C0

Element 5

F7

F6

F5

F4

F3

F2

F1

F0

r

r

DCE

TE

r

r

C1

C0

r: reserved
C1/C0: Class level, 0 to 3
TE: Trigger Event for the point (In Series B)
DCE: Disable Change of state Event for the point (In Series B)
For other Inputs, Element _0 for data index 0
F7-F0: Object Flags, FLAG7/FLAG6/FLAG5/LOCAL_FORCED/REMOTE_FORCED/COMM_LOST/RESTART/ONLINE