Multiple Cable Connection

When connecting multiple cables to the DH-485 connector, use the following
diagram.

Grounding and Terminating the DH-485 Network

Only one connector at the end of the link must have Terminals 1 and 2 jumpered
together. This provides an earth ground connection for the shield of the
communication cable.

Both ends of the network must have Terminals 5 and 6 jumpered together, as
shown below. This connects the termination impedance (of 120 ohm) that is
built into each AIC+ or the 1763-NC01 cable as required by the DH-485
specification.

Connections using Belden #3106A Cable

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue

Blue

Terminal 3 - (Common)

White/Orange

White with Orange Stripe

Terminal 4 - (Data B)

Orange with White Stripe

Terminal 5 - (Data A)

Connections using Belden #9842 Cable

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue/White

White with Blue Stripe

Cut back - no connection

(1)

(1)

To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.

Blue with White Stripe

Terminal 3 - (Common)

White/Orange

White with Orange Stripe

Terminal 4 - (Data B)

Orange with White Stripe

Terminal 5 - (Data A)

to Next Device

to Previous Device