Validating the System

The example systems shown in the tables below are verified to be acceptable
configurations. The systems are valid because:

Calculated Current Values < Maximum Allowable Current Values

Calculated System Loading < Maximum Allowable System Loading

System Loading Worksheet

The tables below are provided for system loading validation. See System Loading
Example Calculations on page 344.

Current Loading

Validating Systems using 1766-L32AWA, or 1766-L32BXB

Maximum Allowable Values

Calculated Values

Current:

Current (Subtotal from Table on page 344.):

1225 mA @ 5V DC

1155 mA @ 24V DC

0 mA + 260 mA = 260 mA @ 5V DC

0 mA + 180 mA = 180 mA @ 24V DC

System Loading:

System Loading:

33.845 W

= (260 mA x 5V) + (180 mA x 24V)
= (1,300 mW) + (4,320 mW)
= 5,620 mW
= 5.62 W

Validating Systems using 1766-L32BWA

Maximum Allowable Values

Calculated Values

Current for Devices Connected to the +24V DC
Sensor Supply:

Sum of all sensor currents

250 mA @ 24V DC

140 mA @ 24V DC (example sensor value)

Current for MicroLogix Accessories and Expansion
I/O:

Current Values (Subtotal from Table ):

1225 mA @ 5V DC

1155 mA @ 24V DC

0 mA + 260 mA = 260 mA @ 5V DC

0 mA + 180 mA = 180 mA @ 24V DC

System Loading:

System Loading:

39.845 W

= (140 mA x 24V) + (260 mA x 5V) + (180 mA x 24V)
= (3,360 mW) + (1,300 mW) + (4,320 mW)
= 8,980 mW
= 8.98 W

Calculating the Current for Expansion I/O

Catalog Number

(1)

n

A

B

n x A

n x B

Number of
Modules

Device Current Requirements

Calculated Current

@ 5V DC (mA)

@ 24V DC (mA)

@ 5V DC (mA)

@ 24V DC (mA)

1762-IA8

50

0

1762-IF4

40

50

1762-IF2OF2

40

105

Advertising