Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

245

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

If this bit is set, the Online bit in the status flag of each Binary Output points is
set when you read Binary Output Status objects.

Binary Command - Control relay output block (CROB)

The MicroLogix 1400 has three control models for Binary Output Control.
They are Activation model, Complementary latch model and Complementary
two-output model.

For the Complementary two-output model, two bits are required to control this
model in the Binary output object. The point index is different than in the
Activation or Complementary latch model. The point index varies as shown in
the table below. The maximum number of Binary Output index for
Complementary two-output model is 2048.

Binary Output Database Index

Activation model or Complementary latch model

Complementary two-output model

0

BO Index 0

BO Close Index 0

1

BO Index 1

BO Trip Index 0

2

BO Index 2

BO Close Index 1

3

BO Index 3

BO Trip Index 1

4

BO Index 4

BO Close Index 2

5

BO Index 5

BO Trip Index 2

4094

BO Index 4094

BO Close Index 2047

4095

BO Index 4095

BO Trip Index 2047