Controller error recovery model – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 200

Advertising
background image

160

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix C Troubleshooting Your System

Controller Error Recovery
Model

Use the following error recovery model to help you diagnose software and
hardware problems in the micro controller. The model provides common
questions you might ask to help troubleshoot your system. Refer to the
recommended pages within the model for further help.

If the LEDS
indicate:

The Following Error
Exists

Probable Cause

Recommended Action

All LEDs off

No input power or
power supply error

No line Power

Verify proper line voltage and connections to the controller.

Power Supply
Overloaded

This problem can occur intermittently if power supply is overloaded when
output loading and temperature varies.

Power and FAULT
LEDs on solid

Hardware faulted

Processor Hardware
Error

Cycle power. Contact your local Allen-Bradley representative if the error
persists.

Loose Wiring

Verify connections to the controller.

Power LED on and
FAULT LED flashing

Application fault

Hardware/Software
Major Fault Detected

For error codes and Status File information, see MicroLogix 1400
Programmable Controllers Instruction Set Reference Manual
, Publication

1766-RM001

.

RUN
FORCE
FAULT LEDs all
flashing

Operating system fault

Missing or Corrupt
Operating System

See Recovering from Missing or Corrupt OS State on page D-182.

Advertising