Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 179

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

137

Specifications Appendix A

Output Specifications

Specification

1762-OA8

1762-OB8

1762-OB16

1762-OB32T

1762-OV32T

Shipping weight, approx.
(with carton)

215 g (0.48 lbs.)

210 g (0.46 lbs.)

235 g (0.52 lbs.)

200 g (0.44 lbs.)

200 g (0.44 lbs.)

Voltage category

100…240V AC

24V DC

24V DC

24V DC source

24V DC sink

Operating voltage range

85…265V AC at
47…63 Hz

20.4…26.4V DC

20.4…26.4V DC

10.2…26.4V DC

10.2…26.4V DC

Number of outputs

8

8

16

32

32

Bus current draw, max.

115 mA at 5V DC
(0.575 W)

115 mA at 5V DC
(0.575 W)

175 mA at 5V DC (0.88
W)

175 mA at 5V DC
0 mA at 24V DC

175 mA at 5V DC
0 mA at 24V DC

Heat dissipation, max.

2.9 W

1.61 W

2.9 W at 30 °C (86 °F)
2.1 W at 55 °C (131 °F)

3.4 W at 26.4 DC

2.7 W at 26.4V DC

Signal delay, max. –
resistive load

On delay: 1/2 cycle
Off delay: 1/2 cycle

On delay: 0.1 ms
Off delay: 1.0ms

On delay: 0.1 ms
Off delay: 1.0 ms

On delay: 0.5 ms
Off delay: 4.0 ms

On delay: 0.5 ms
Off delay: 4.0 ms

Off-state leakage current,
max.

2 mA at 132V,
2.5 mA at 265V

1.0 mA

1.0 mA

0.1 mA at 26.4V DC

0.1 mA at 26.4V DC

On-state current, min.

10 mA

1.0 mA

1.0 mA

1.0 mA

1.0 mA

On-state voltage drop,
max.

1.5V at 0.5 A

1.0V DC

1.0V DC

0.3V DC at 0.5 A

0.3V DC at 0.5A

Continuous current per
point, max.

0.25 A at 55 °C
(131 °F)
0.5 A at 30 °C (86 °F)

0.5 A at 55 °C (131 °F)
1.0 A at 30 °C (86 °F)

0.5 A at 55 °C (131 °F)
1.0 A at 30 °C (86 °F)

0.5 A at 60 °C (140 °F)

0.5A at 60 °C (140 °F)

Continuous current per
common, max.

1.0 A at 55 °C (131 °F)
2.0 A at 30 °C (86 °F)

4.0 A at 55 °C (131 °F)
8.0 A at 30 °C (86 °F)

4.0 A at 55 °C (131 °F)
8.0 A at 30 °C (86 °F)

2.0 A at 60 °C (140 °F)

2.0 A at 60 °C (140 °F)

Continuous current per
module, max.

2.0 A at 55 °C (131 °F)
4.0 A at 30 °C (86 °F)

4.0 A at 55 °C;
8.0 A at 30 °C

4.0 A at 55 °C (131 °F)
8.0 A at 30 °C (86 °F)

4.0 A at 60 °C (140 °F)

4.0 A at 60 °C (140 °F)

Surge current, max.

5.0 A (Repeatability is
once every 2 s for a
duration of 25 ms.

2.0 A (Repeatability is
once every 2 s at
55 °C (131 °F), once
every second at 30 °C
(86 °F) for a duration
of 10 ms.)

2.0 A (Repeatability is
once every 2 s at
55 °C (131 °F), once
every second at 30 °C
(86 °F) for a duration
of 10 ms.)

2.0 A (Repeatability is
once every 2 s at
60 °C (140 °F) for
10 ms)

2.0 A (Repeatability is
once every 2 s at
60 °C (140 °F) for
10 ms)

Isolated groups

Group 1: Outputs 0 to
3
Group 2: Outputs 4 to
7

Group 1: Outputs 0 to
7

Group 1: Outputs 0 to
15

Group 1: Outputs 0…15
Group 2: Outputs 16…31 (internally connected
to common)

Output group to
backplane isolation

Verified by one of the
following dielectric
tests: 1836V AC for 1 s
or 2596V DC for 1 s.
265V AC working
voltage (IEC Class 2
reinforced insulation)

Verified by one of the following dielectric tests:
1200V AC for 1 s or 1697V DC for 1 s.
75V DC working voltage (IEC Class 2 reinforced
insulation)

Verified by one of the following dielectric tests:
1200V AC for 2 s or 1697V DC for 2 s.
75V DC working voltage (IEC Class 2 reinforced
insulation)

Output group to output
group isolation

Verified by one of the
following dielectric
tests: 1836V AC for 1 s
or 2596V DC for 1 s.
265V AC working
voltage (IEC Class 2
reinforced insulation)

Not applicable

Verified by one of the following dielectric tests:
1200V AC for 2 s or 1697V DC for 2 s.
75V DC working voltage (IEC Class 2 reinforced
insulation)

Advertising