138

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix A Specifications

Vendor I.D. code

1

Product type code

7

Product code

119

101

103

100

102

Output Specifications

Specification

1762-OA8

1762-OB8

1762-OB16

1762-OB32T

1762-OV32T

Output Specifications

Specification

1762-OW8

1762-OW16

1762-OX6I

1762-IQ8OW6

Shipping weight, approx.
(with carton)

228 g (0.50 lbs.)

285 g (0.63 lbs.)

220 g (0.485 lbs)

280 g (0.62 lbs.)

Voltage category

AC/DC normally open
relay

AC/DC normally open
relay

AC/DC Type C Relay

AC/DC normally open
relay

Operating voltage range

5…265V AC
5…125V DC

5…265V AC
5…125V DC

5…265V AC
5…125V DC

5…265V AC
5…125V DC

Number of outputs

8

16

6

6

Bus current draw, max.

80 mA at 5V DC
(0.40W)
90 mA at 24V DC
(2.16W)

140 mA at 5V DC
(0.70W)

(1)

180 mA at 24V DC
(4.32W)

(1)

110 mA at 5V DC
(0.55W)
110 mA at 24V DC
(2.64W)

110 mA at 5V DC
80 mA at 24V DC

Heat dissipation, max.

2.9 W

6.1 W

(1)

2.8 W

5.0 W at 30V DC
4.4 W at 26.4V DC
(The Watts per point,
plus the minimum W,
with all points
energized.)

Signal delay, max. –
resistive load

On Delay: 10 ms
Off Delay: 10 ms

On Delay: 10 ms
Off Delay: 10 ms

On Delay: 10 ms (max)
6 ms (typical)
Off Delay: 20 ms (max)
12 ms (typical)

On-delay: 10 ms (max)
Off-delay: 10 ms (max)

Off-state leakage, max.

0 mA

0 mA

0 mA

0 mA

On-state current, min.

10 mA

10 mA

100 mA

10 mA

On-state voltage drop,
max.

Not Applicable

Continuous current per
point, max.

2.5 A (Also see “Relay Contact Ratings” on page
139.)

7 A (Also see “Relay
Contact Ratings” on
page 139.)

2.5 A (Also see “Relay
Contact Ratings” on
page 139.)

Continuous current per
common, max.

8 A

8 A

7 A (Also see “Relay
Contact Ratings” on
page 133.)

8 A

Continuous current per
module, max.

16 A

16 A

30A (Also see

Module

Load Ratings
1762-OX6I on page
140

.)

8A

Surge current, max.

See “Relay Contact Ratings” on page 139.

See “Relay Contact
Ratings” on page 139.

See “Relay Contact
Ratings” on page 139.

Isolated groups

Group 1: Outputs 0 to
3
Group 2: Outputs 4 to
7

Group 1: Outputs 0 to
7
Group 2: Outputs 8 to
15

All 6 Outputs
Individually Isolated.

Group 3:
Outputs 0 to 5

Output group to
backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 s or 2596V DC for 1 s.
265V AC working voltage (IEC Class 2 reinforced insulation)

Advertising