272

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)

There are some rules for the Object flag set or clear for each bit by the controller.
The rules below are also applied to Event data.

• When the controller is in Non-Executing mode, the object flag is always all

0.

• When the controller is in Executing mode and there is no configuration

file, only the Online flag in the object flag is set.

• When the controller is in Executing mode and there is a configuration file,

the flags in the object flag are set according to the upper byte of the
configuration files.

Object Flags for Binary Input

Bit Offset

Name

Description

0

ONLINE

In Series A controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode.
In Series B controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode and the configuration file does not
exist. May be 1 when the controller is or was in Executing mode and the configuration
file exists.

1

RESTART

Always 0. Not used.

2

COMM_LOST

Always 0. Not used.

3

REMOTE_FORCED

Always 0. Not used.

4

LOCAL_FORCED

Always 0. Not used.

5

CHATTER_FILTER

Always 0. Not used.

6

reserved

Always 0. Not used.

7

STATE

Reflects point state of Binary Input point.

Object Flags for Double Binary Input

Bit Offset

Name

Description

0

ONLINE

In Series A controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode.
In Series B controllers:
0 when the controller is or was in Non-Execting mode.
1 when the controller is or was in Executing mode and the configuration file does not
exist. May be 1 when the controller is or was in Executing mode and the configuration
file exists.

1

RESTART

Always 0. Not used.

2

COMM_LOST

Always 0. Not used.

3

REMOTE_FORCED

Always 0. Not used.

4

LOCAL_FORCED

Always 0. Not used.

5

CHATTER_FILTER

Always 0. Not used.

6

STATE

Reflects point state of Double-Bit Binary Input point. Double-bit LSB.

7

STATE

Reflects point state of Double-Bit Binary Input point. Double-bit MSB