Chapter 2 Install Your Controller

Use only the following communication cables in Class I, Division 2 hazardous
locations.

Disconnecting Main Power

The main power disconnect switch should be located where operators and
maintenance personnel have quick and easy access to it. In addition to
disconnecting electrical power, all other sources of power (pneumatic and
hydraulic) should be de-energized before working on a machine or process
controlled by a controller.

Safety Circuits

Circuits installed on the machine for safety reasons, like overtravel limit switches,
stop push buttons, and interlocks, should always be hard-wired directly to the
master control relay. These devices must be wired in series so that when any one
device opens, the master control relay is de-energized, thereby removing power to
the machine. Never alter these circuits to defeat their function. Serious injury or
machine damage could result.

Power Distribution

There are some points about power distribution that you should know:

Environment Classification

Communication Cables

Class I, Division 2 Hazardous Environment

1761-CBL-AC00 Series C or later

1761-CBL-AM00 Series C or later

1761-CBL-AP00 Series C or later

1761-CBL-PM02 Series C or later

1761-CBL-HM02 Series C or later

2707-NC9 Series C or later

1763-NC01 Series A or later

1747-CP3 Series

WARNING: Explosion Hazard
Do not replace components, connect equipment, or disconnect
equipment unless power has been switched off.

WARNING: Explosion Hazard
Do not connect or disconnect connectors while circuit is live.