165

Troubleshooting Your System Appendix C

Calling Rockwell
Automation for Assistance

If you need to contact Rockwell Automation or local distributor for assistance, it
is helpful to obtain the following (prior to calling):

• controller type, series letter, revision letter, and firmware (FRN) number of

the controller

• controller indicator status

Hardware-Specific
Error

X210

001

0 0001 0000

Reserved

Configuration Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

Invalid input data format selected (channel 0)

X402

010

0 0000 0010

Invalid input data format selected (channel 1)

X403

010

0 0000 0011

Invalid output data format selected (channel 0)

X404

010

0 0000 0100

Invalid output data format selected (channel 1)

(1)

X represents “Don’t Care”.

Extended Error Codes for 1762-IF2OF2

Error Type

Hex Equivalent

(1)

Module Error
Code

Extended Error
Information Code

Error Description

Binary

Binary

Extended Error Codes for 1762-IF4 and 1762-OF4

Error Type

Hex Equivalent

(1)

Module
Error Code

Extended Error
Information Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-
Specific Error

X300

001

1 0000 0000

Reserved

Configuration Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

Invalid range select (Channel 0)

X402

010

0 0000 0010

Invalid range select (Channel 1)

X403

010

0 0000 0011

Invalid range select (Channel 2)

X404

010

0 0000 0100

Invalid range select (Channel 3)

X405

010

0 0000 0101

Invalid filter select (Channel 0) – 1762-IF4 only

X406

010

0 0000 0110

Invalid filter select (Channel 1) – 1762-IF4 only

X407

010

0 0000 0111

Invalid filter select (Channel 2) – 1762-IF4 only

X408

010

0 0000 1000

Invalid filter select (Channel 3) – 1762-IF4 only

X409

010

0 0000 1001

Invalid format select (Channel 0)

X40A

010

0 0000 1010

Invalid format select (Channel 1)

X40B

010

0 0000 1011

Invalid format select (Channel 2)

X40C

010

0 0000 1400

Invalid format select (Channel 3)

(1)