Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 339

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

299

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

49

CS0:49

CS2:49

RTS Send Delay

50

CS0:50

CS2:50

RTS Off Delay

51

CS0:51

CS2:51

bits 0-7: Baud Rate
bits 8-9: Parity
bits 10-15: Reserved - Always 0

52

CS0:52

CS2:52

List Category ID (6)

53

CS0:53

CS2:53

Length (32)

54

CS0:54

CS2:54

Format Code (2)

55

CS0:55

CS2:55

Application Layer Error Codes
0: NO_ERROR - No error found in the Application Layer.
1: FC_CANNOT_BROADCAST - Reserved
2: FC_NOT_SUPPORTED - The received packet has unsupported Function Code.
3: OBJ_NOT_SUPPORTED - The received packet has unsupported object(s).
4: BAD_REQUEST_LENGTH - Reserved
5: CONFIGURATION_ERROR - The error was caused by the invalid configuration
during packet generating. E.g. invalid Data Set Configuration.
6: BAD_PARAMETER - The received packet has invalid parameters except Function
Code and Object Codes. E.g. invalid Qualifier codes.
7: BAD_FILE_TYPE - The error was caused by invalid configuration in DNP3 Slave
Application Layer. Invalid File Type specified.
8: BAD_FILE_NUMBER - The error was caused by invalid configuration in DNP3
Slave Application Layer. Invalid File Number specified.
9: BAD_DNP3_ADDRESS - The error was caused by invalid configuration in DNP3
Slave Application Layer. Invalid File Number specified.
10: TABLE_WRITE_PROTECTED - The specified DNP3 object data file has been
locked to be written.
11: TABLE_ACCESS_DENIED - The specified DNP3 object data file has been locked
to be read or written.
12: TABLE_OWNERSHIP_ERROR - The specified DNP3 object data file has been
locked to be read or written.
If an error code is within 6 to 12, related file number and element number are
shown in word 59 and 60.

56

CS0:56

CS2:56

Application Layer Error Count

57

CS0:57

CS2:57

Function Code that caused the last error

58

CS0:58

CS2:58

Last Transmitted IIN in the response

59

CS0:59

CS2:59

Data file number of last error request

60

CS0:60

CS2:60

Data element number of last error request

61

CS0:61

CS2:61

Received Confirm Function Code Counter

62

CS0:62

CS2:62

Received Read Function Code Counter

63

CS0:63

CS2:63

Received Write Function Code Counter

64

CS0:64

CS2:64

Received Etc Function Code Counter

65

CS0:65

CS2:65

Transmitted Solicited Response Function Code Counter

66

CS0:66

CS2:66

Transmitted Unsolicited Response Function Code Counter

67

CS0:67

CS2:67

Number of events to be reported

Communication Status File Words

Words Offset

File/Element
Description for
Channel 0

File/Element
Description for
Channel 2

Description

Advertising
This manual is related to the following products: