See table 146 – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 188

Advertising
background image

146

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Appendix A Specifications

1762-IT4 Repeatability at 25 °C (77 °F)

(1)

(2)

(1) Repeatability is the ability of the input module to register the same reading in successive measurements for the

same input signal.

(2) Repeatability at any other temperature in the 0...60 °C (32...140 °F) range is the same as long as the

temperature is stable.

Input Type

Repeatability for 10
Hz Filter

Thermocouple J

±0.1 °C [±0.18 °F]

Thermocouple N (-110…1300 °C [-166…2372 °F])

±0.1 °C [±0.18 °F]

Thermocouple N (-210…-110 °C [-346…-166 °F])

±0.25 °C [±0.45 °F]

Thermocouple T (-170…400 °C [-274…752 °F])

±0 .1 °C [±0.18 °F]

Thermocouple T (-270…-170 °C [-454…-274 °F])

±1.5 °C [±2.7 °F]

Thermocouple K (-270…1370 °C [-454 °F…2498 °F])

±0.1 °C [±0.18 °F]

Thermocouple K (-270…-170 °C [-454…-274 °F])

±2.0 °C [±3.6 °F]

Thermocouple E (-220…1000 °C [-364…1832 °F])

±0.1 °C [±0.18 °F]

Thermocouple E (-270…-220 °C [-454…-364 °F])

±1.0 °C [±1.8 °F]

Thermocouples S and R

±0.4 °C [±0.72 °F]

Thermocouple C

±0.2 °C [±0.36 °F]

Thermocouple B

±0.7 °C [±1.26 °F]

±50 mV

±6

μV

±100 mV

±6

μV

1762-IT4 Accuracy

Input Type

(1)

With Autocalibration Enabled

Without Autocalibration

Accuracy

(2)

(3)

for 10 Hz, 50 Hz and 60 Hz

Filters (max.)

Maximum Temperature Drift

(2)

(4)

at 25 °C [77 °F]
Ambient

at 0…60 °C
[32…140 °F]
Ambient

at 0…60 °C [32…140 °F]
Ambient

Thermocouple J (-210…1200 °C [-346…2192 °F])

±0.6 °C [± 1.1 °F]

±0.9 °C [± 1.7 °F]

±0.0218 °C/ °C [±0.0218 °F/ °F]

Thermocouple N (-200…1300 °C [-328…2372 °F])

±1 °C [± 1.8 °F]

±1.5 °C [±2.7 °F]

±0.0367 °C/ °C [±0.0367 °F/ °F]

Thermocouple N (-210…-200 °C [-346…-328 °F])

±1.2 °C [±2.2 °F]

±1.8 °C [±3.3 °F]

±0.0424 °C/ °C [±0.0424 °F/ °F]

Thermocouple T (-230…400 °C [-382…752 °F])

±1 °C [± 1.8 °F]

±1.5 °C [±2.7 °F]

±0.0349 °C/ °C [±0.0349 °F/ °F]

Thermocouple T (-270…-230 °C [-454…-382 °F])

±5.4 °C [± 9.8 °F]

±7.0 °C [±12.6 °F]

±0.3500 °C/ °C [±0.3500 °F/ °F]

Thermocouple K (-230…1370 °C [-382…2498 °F])

±1 °C [± 1.8 °F]

±1.5 °C [±2.7 °F]

±0.4995 °C/ °C [±0.4995 °F/ °F]

Thermocouple K (-270…-225 °C [-454…-373 °F])

±7.5 °C [± 13.5 °F]

±10 °C [± 18 °F]

±0.0378 °C/ °C [±0.0378 °F/ °F]

Thermocouple E (-210…1000 °C [-346…1832 °F])

±0.5 °C [± 0.9 °F]

±0.8 °C [±1.5 °F]

±0.0199 °C/ °C [±0.0199 °F/ °F]

Thermocouple E (-270…-210 °C [-454…-346 °F])

±4.2 °C [± 7.6 °F]

±6.3 °C [±11.4 °F]

±0.2698 °C/ °C [±0.2698 °F/ °F]

Thermocouple R

±1.7 °C [± 3.1 °F]

±2.6 °C [± 4.7 °F]

±0.0613 °C/ °C [±0.0613 °F/ °F]

Thermocouple S

±1.7 °C [± 3.1 °F]

±2.6 °C [± 4.7 °F]

±0.0600 °C/ °C [±0.0600 °F/ °F]

Thermocouple C

±1.8 °C [±3.3 °F]

±3.5 °C [±6.3 °F]

±0.0899 °C/ °C [±0.0899 °F/ °F]

Advertising
This manual is related to the following products: