Working voltage – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 175

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

133

Specifications Appendix A

Working Voltage

Analog Input Filter Settings

Analog Input Filter Settings

Filter Bandwidth (-3dB Freq Hz)

Sampling Frequency

250 Hz

250 Hz

1 kHz

60 Hz

60 Hz

1 kHz

50 Hz

50 Hz

1 kHz

10 Hz

10 Hz

1 kHz

Relay Contact Ratings

Maximum Volts

Amperes

Amperes
Continuous

(1)

Volt-Amperes

Make

Break

Make

Break

240V AC

15.0 A

1.5 A

5.0 A

(2)

/3.0 A

3600 VA

360 VA

120V AC

30.0 A

3.0 A

5.0 A

(2)

/3.0 A

3600 VA

360 VA

125V AC

0.22 A

(3)

1.0 A

28 VA

(1) 5.0 A for UL 508

3. 0A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D

(2) 3.0 A above 40 °C.(104 °F)

(3) For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by

the applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the
make/break ratings for relay contacts cannot exceed 2A.

Working Voltage for 1766-L32AWA/A

Description

Recommendation

Power Supply Input to Backplane
Isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Backplane Isolation

Verified by one of the following dielectric tests:1517V AC for 1 second or 2145V DC for 1 second

132V AC Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Input Group Isolation

Verified by one of the following dielectric tests:1517V AC for 1 second or 2145V DC for 1 second

132V AC Working Voltage (basic insulation)

Output Group to Backplane Isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Output Group to Output Group Isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or 2596V DC for 1second

265V AC Working Voltage (basic insulation), 150V AC Working Voltage (IEC Class 2 reinforced insulation)

Working Voltage for 1766-L32BWA/A

Description

Recommendation

Power Supply Input to Backplane
Isolation

Verified by one of the following dielectric tests:1836V AC for 1 second or 2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Input Group to Backplane Isolation
and Input Group to Input Group
Isolation

Verified by one of the following dielectric tests: 1100V AC for 1 second or 1697V DC for 1 second

75V DC Working Voltage (IEC Class 2 reinforced insulation)