Chapter 3 Wire Your Controller

Figure 27 - 1762-IQ8OW6 Wiring Diagram

Analog Wiring

Consider the following when wiring your analog modules:

• The analog common (COM) is not connected to earth ground inside the

module. All terminals are electrically isolated from the system.

• Channels are not isolated from each other.
• Use Belden 8761, or equivalent, shielded wire.
• Under normal conditions, the drain wire (shield) should be connected to

the metal mounting panel (earth ground). Keep the shield connection to
earth ground as short as possible.

• To ensure optimum accuracy for voltage type inputs, limit overall cable

impedance by keeping all analog cables as short as possible. Locate the I/O
system as close to your voltage type sensors or actuators as possible.

• The module does not provide loop power for analog inputs. Use a power

supply that matches the input transmitter specifications.

1762-IF2OF2 Input Type Selection

Select the input type, current or voltage, using the switches located on the
module’s circuit board

and the input type/range selection bits in the

Configuration Data File. Refer to MicroLogix

1400 Programmable Controllers

Instruction Set Reference Manual, publication

1766-RM001

. You can access the

switches through the ventilation slots on the top of the module. Switch 1 controls

IN 6

IN 4

IN 3

IN 1

IN 5

IN 2

IN 0

OUT 4

OUT 2

OUT 0

VAC

VDC

VAC

VDC

DC

COM 1

OUT 3

OUT 1

IN 7

L1 or +DC

L1 or +DC

-DC (Sinking)
+DC (Sourcing)

Connected Internally

+DC (Sinking)
-DC (Sourcing)

L2 or -DC

OUT 5

+DC (Sinking)
-DC (Sourcing)

-DC (Sinking)
+DC (Sourcing)

DC

COM 0

CR

CR

CR

CR

44579