Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 173

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

131

Specifications Appendix A

Figure 2 - 1766-L32BXB, 1766-L32BXBA FET Output
Maximum output current (temperature dependent):

Description

General Operation High Speed Operation

(1)

(Output 2, 3 and 4 Only)

(1) Output 2, 3 and 4 are designed to provide increased functionality over the other FET outputs. Output 2, 3 and 4

may be used like the other FET transistor outputs, but in addition, within a limited current range, they may be
operated at a higher speed. Output 2, 3 and 4 also provide a pulse train output (PTO) or pulse width modulation
output (PWM) function.

Power supply voltage

24V DC (-15%, 10%) Class 2

On-state voltage drop:
at max load current
at max surge current

1V DC
2.5V DC

Not Applicable
Not Applicable

Current rating per point
max load
min load
max leakage

See graphs above
1.0 mA
1.0 mA

100 mA
20 mA
1.0 mA

Surge current per point:
peak current
max surge duration
max rate of repetition at 30 °C (86 °F)
max rate of repetition at 60 °C (140 °F)

4.0 A
10 ms
once every second
once every 2
seconds

Not Applicable
Not Applicable
Not Applicable
Not Applicable

Turn-On Time (maximum)

11

μs

28 ns

Turn-Off Time (maximum)

89

μs

2.3

μs

0.25

10°C

(50°F)

30°C

(86°F)

50°C

(122°F)

0.75A, 60°C (140°F)

1.5A, 30°C (86°F)

70°C

(158°F)

80°C

(176°F)

0.5

0.75

1.0

1.25

1.5

1.75

2.0

1.0

10°C

(50°F)

30°C

(86°F)

50°C

(122°F)

3.0A , 60°C (140°F)

6.0A , 30°C (86°F)

70°C

(158°F)

80°C

(176°F)

2.0

3.0

4.0

5.0

6.0

7.0

8.0

FET Current per Point

FET Total Current

Cu

rrent (Amps)

Cu

rrent (Amps)

Temperature

Temperature

Valid
Range

Valid
Range

44532