Loss of power source, Input states on power down, Other types of line conditions – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 26: Preventing excessive heat

Advertising
background image

12

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 2 Install Your Controller

• The power-up sequence of devices in a system.
• The amount of the power source voltage sag if the inrush current cannot be

supplied.

• The effect of voltage sag on other equipment in the system.

If the entire system is powered-up at the same time, a brief sag in the power source
voltage typically will not affect any equipment.

Loss of Power Source

The power supply is designed to withstand brief power losses without affecting
the operation of the system. The time the system is operational during power loss
is called program scan hold-up time after loss of power. The duration of the
power supply hold-up time depends on the type and state of the I/O, but is
typically between 10 milliseconds and 3 seconds. When the duration of power
loss reaches this limit, the power supply signals the processor that it can no longer
provide adequate DC power to the system. This is referred to as a power supply
shutdown. The processor then performs an orderly shutdown of the controller.

Input States on Power Down

The power supply hold-up time as described above is generally longer than the
turn-on and turn-off times of the inputs. Because of this, the input state change
from “On” to “Off ” that occurs when power is removed may be recorded by the
processor before the power supply shuts down the system. Understanding this
concept is important. The user program should be written to take this effect into
account.

Other Types of Line Conditions

Occasionally the power source to the system can be temporarily interrupted. It is
also possible that the voltage level may drop substantially below the normal line
voltage range for a period of time. Both of these conditions are considered to be a
loss of power for the system.

Preventing Excessive Heat

For most applications, normal convective cooling keeps the controller within the
specified operating range. Ensure that the specified temperature range is
maintained. Proper spacing of components within an enclosure is usually
sufficient for heat dissipation.

In some applications, a substantial amount of heat is produced by other
equipment inside or outside the enclosure. In this case, place blower fans inside

Advertising
This manual is related to the following products: