End-of-line termination, Connecting the aic – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 90

Advertising
background image

76

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

Chapter 4 Communication Connections

End-of-Line Termination

MicroLogix 1400 Channel 0 to DH-485 Communication Cable Pinout

When connecting MicroLogix 1400 Channel 0 to DH-485 communication
cable pinout using an RS-232 cable, the maximum that the cable length may be
extended is 15.24 m (50 ft). Refer to the following typical pinout:

Connecting the AIC+

You can connect a MicroLogix 1400 controller to a DH-485 network via
Channel 0 directly without using an optical isolator, such as AIC+, catalog
number 1761-NET-AIC, because Channel 0 is isolated. However, you need to
use an AIC+ to connect your PC or other MicroLogix Family products, such as
MicroLogix 1200, to a DH-485 network.

Jumper

Jumper

Belden #3106A or #9842 Cable
1219 m (4000ft) Maximum

Jumper

DTE Device
(MicroLogix
1400
Channel 0)

DCE Device (DH-485
connector)

8-Pin

6-pin

7

TXD

6

Termination

4

RXD

5

A

2

GND

4

B

1

B(+)

3

Common

8

A(-)

2

Shield

5

DCD

1

ChassisGround

6

CTS

3

RTS