Appendix G Connecting to Networks via Ethernet Interface

Cables

Shielded and non-shielded twisted-pair 10/100Base-T cables with RJ45
connectors are supported. The maximum cable length between an MicroLogix
1400 Ethernet port and a 10/100Base-T port on an Ethernet hub or switch
(without repeaters or fiber) is 100 m (323 ft). However, in an industrial
application, cable length should be kept to a minimum.

Straight-through cabling

The standard Ethernet cable is terminated in accordance with EIA/TIA 568B on
both ends. The crossover cable is terminated to EIA/TIA 568B at one end and
EIA/TIA 568A at the other, exactly as shown in the two color coded plugs below.

The following figures show how the TIA/EIA 568A and 568B are to be
terminated. There are four pairs of wires contained in a CAT5 UTP cable. These
pairs of cables are color coded white blue/blue, white orange/orange, white

IMPORTANT

When connecting the MicroLogix 1400 Ethernet port to a
10/100Base-T Ethernet switch, note the following recommendations:

·

Use the auto negotiation function for both the switch port and the
MicroLogix 1400 Ethernet port

·

If you want to force to a specific speed/duplex mode, you must
force both the MicroLogix 1400 Ethernet port and the switch port
to the same setting.

TIP

The Ethernet cabling with straight-through method is recommended
as below. Do not make the incorrect connection.

Pin

Pin Name

Cable color

1

Tx+ Orange/White

2

Tx- Orange

3

Rx+ Green/White

4

No used by 10/100Base-T

Blue

5

No used by 10/100Base-T

Blue/White

6

Rx-

Green

7

No used by 10/100Base-T

Brown/White

8

No used by 10/100Base-T

Brown