Dnp3 data set object – Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual

Page 301

Advertising
background image

Rockwell Automation Publication 1766-UM001H-EN-P - May 2014

261

MicroLogix 1400 Distributed Network Protocol (DNP3) Appendix F

DNP3 Data Set Object

This feature is supported only in MicroLogix 1400 Series B controllers.

These object groups and variations are supported.

Data Set Objects:

• g85v0 - Data Set Prototype - Any Variation
• g85v1 - Data Set Prototype - With UUID
• g86v1 - Data Set Descriptor - Data set contents
• g86v2 - Data Set Descriptor - Characteristics
• g87v0 - Static Data Set - Any Variation
• g87v1 - Static Data Set - Present value
• g88v0 - Event Data Set - Any Variation
• g88v1 - Event Data Set - Snapshot

Related Object/Configuration File Number:

• Data Set Prototypes Object File Number
• Data Set Descriptors Object File Number

To generate a Data Set Object from the DNP3 Subsystem in the controller,
configure Data Set Prototypes/Descriptors Object File Number in the DNP3
Slave Application Layer Configuration file and also the Maximum Number of
Data Set Prototypes/Descriptors Files.

Each Data Set Prototypes Object file (N data file) can have up to 10 elements of
Data Set Prototypes, and each Data Set Descriptors Object file (N data file) can
have up to 10 elements of Data Set Descriptors.

As an example, with Data Set Prototypes files, if you configure "Data Set
Prototypes Object File Numbers" to 50 and "Maximum Number of Data Set

Advertising